Tyco Water Home | Products | Product News | Project News | Export | TFC Pacific

Search 

 
Ductile Iron Pipelines Sintakote Steel Pipelines Plastic Pipeline Systems Pipeline Components Services Contact Us
Services : Complete Tapping Service : Tappings : Tapping Requirements

Complete Tapping Service

Tapping Requirements

 

  • To perform a tapping, CTS requires the main to be excavated and exposed as detailed:
    • CTS must have access 100mm below the pipe.
    • All statutory requirements regarding trenching must be complied with.
    • Other services may be in the excavation area provided they are not on the same elevation as the pipe to be tapped.
    • Maximum length from the main to the end of the valve off - take is 450mm.
    • Minimum trench length from the edge of the pipe 1300mm, in the off-take direction.
    • Minimum of 100mm clearance on opposite side of pipe.

Excavation Requirements:

The pipe to be tapped is to be exposed 300mm all round.

Tapping Size

Length (L)

Width (W)

DN 80mm - DN 225mm

1300mm

800mm

DN 250mm - DN 300mm

2000mm

1200mm

DN 375mm - DN 450mm

3000mm

1200mm

L = The distance perpendicular to the pipe being tapped.

W = The width of the Excavation

 